Separatoare de sarcina pentru sigurante MPR - 160 A

QUADRON®CrossLinkBreaker - Separatoare de sarcina MPR - 160 A:

  • Separatoare de sarcina MPR de marime 00
  • 3 poli
  • Terminale cu protectie
  • Carcasa de protectie

Separatoare de sarcina pentru sigurante MPR - 160 A

Description Part No.: 33222
QUADRON®CrossLinkBreaker
NH fuse switch disconnector size 00, 160 A
3-pole, Surface-mounting, screw-type terminal on both sides, with short protection cover
Product Advantages The shock protection cover is in 2 pieces to provide for safe connection of cables.
The lid is provided with self-closing inspection holes.
Product Group Subgroup 9
03
Standards IEC 60947-1:2004
IEC 60947-3:1999
IEC 60947-1:2007
IEC 60947-3:2008
EN 60947-1:2007
EN 60947-3:2009
DIN EN 60947-1/04.08
DIN EN 60947-3/02.10
Approvals IEC (CB), Germanischer Lloyd, GOST, CCC

Type No.: LTS00

CCC certificate: 2004010302117250
Electrical Data 690 V AC / 160 A
type of current AC (50-60Hz) / DC
rated insulation voltage 800V
rated surge withstand capacitiy 6kV
conditional rated short circuit current 50 kA (with fuse links gL/gG)
switching capacity / application categories AC23 B (400 V), AC 23 B (500V / 125A)
AC22 B (690 V), AC21 B (690 V)
DC22 B (220V), DC22 B (440V / 125A), DC21B (440V),
AC20B (1000 V), DC20B (1000 V) pollution degree 2

duty: uninterrupted
(number of operating cycles corresponding to IEC 60947-3)

DC specifications: 2 current paths (L1, L2) in series
for fuse links to IEC 60269-2-1 (I) / DIN VDE 0636-201 size 00 up to 12 W

According to the AC and DC switching characteristics and in consideration of the overload conditions, the following distances to earth metal parts have to be provided. 
- top 150mm, side 55mm
By using as a disconnector (switching not under load) the mentioned distances are not applicable.

Power dissipation:
The power dissipation of the device results in 4,5 W at a typical
load with 80 % of the nominal current.
(The power dissipation is 7 W for application at nominal current.)


Degree of protection IP30 (front side); degree of protection near terminal depends on installation
Mechanical Data Width x Height x Depth (mm): 106 x 151 x 83
Weight (kg/100): 71,9

fastened by screw mounting, clip-on mounting by 33 193
Connections Accessories:
Clamp: Cu 1,5 -70mm² rm, f+AE; la. Cu 12x1-10; 3 Nm tightening torque 
Wedge clamp (single): Cu, Al* 16-70mm² rm, sm, f+AE; 3 Nm tightening torque 
Tunnel clamp: 3x Cu 1,5-16mm² rm, f+AE; 3 Nm tightening torque 

*not maintenance free when aluminium conductors are used
screw M8 : 
Md 12 - 14 Nm
Material Characteristics Main body:
temperature stability 125°C, 
self-extinguishing in acc. to UL 94, 
creepage resistance CTI 200,

Shock protection cover:
temperature stability 120°C, 
self-extinguishing in acc. to UL 94, 
creepage resistance CTI 200
Handle:
temperature stability 120°C, 
self-extinguishing in acc. to UL 94, 
creepage resistance CTI 200
Contacts:
spring-loaded contacts,
copper, silver plated
Pack Size 1
Catalog Page: 2011 : 6/5
Downloads
General technical notes: PDF (67 KB)
CAD-Symbol 2D: DXF (3,6 KB)
Dimensioned Drawing: PDF (121 KB)
Mounting Instructions: PDF (144 KB)
Technical Description: PDF