E2608-NO2

Nitrogen Dioxide Detector

Download documentation (enghlish only):

datasheet E2608-NO2

Nitrogen dioxide detector E2608-NO2 is a member of new PluraSens® family of multifunctional measurement instruments.

Applications include underground parkings, boiler houses, kitchens, and other confined spaces, where potentially toxic concentration of nitrogen dioxide can accumulate.

Two relays with closing contact may be used for remote signalling or ventilation control. The default alarm set-points are typically at 3 ppm and at 6 ppm.

The instrument utilises novel fully calibrated and temperature compensated electrochemical gas sensor with excellent repeatability, stability and long lifetime.

Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.

Nitrogen Dioxide Detector

  • Stable long-life electrochemical cell
  • Detection ranges 0...20 ppm NO2, 0...200 ppm NO2
  • Resolution 0,02 / 0,1 ppm NO2
  • Default alarm set-points 3 ppm / 6 ppm NO2
  • 2 × 4-20 mA / 0-10 V, RS485
Calibration Nitrogen Dioxide NO2
Sensing method Long-life electrochemical sensor
Sampling method diffusion
Detection range Standard 0...20 ppm (100 ppm peak) NO2
  High 0...200 ppm (1000 ppm peak) NO2
Resolution 0,02 / 0,1 ppm NO2
Accuracy < 1 ppm NO2
Sensor lifetime > 2 years
Power supply 11...30 VDC or 90...265 VAC
Digital interface RS485, Modbus RTU protocol
Analog outputs 2 × 4-20 mA / 0-10 V, user settable
Output relays 2 × SPST relays (closing contact),
  250 VAC / 30 VDC, 5 A max
Default alarm set-points 3 ppm /6 ppm NO2
Enclosure Light grey ABS plastic, wall mount, IP65
Dimensions H85 × W82 × D55 mm
Operating conditions -20...+50 °C, 15...90 %RH