Nitrogen Dioxide Detector
Nitrogen dioxide detector E2608-NO2 is a member of new PluraSens® family of multifunctional measurement instruments.
Applications include underground parkings, boiler houses, kitchens, and other confined spaces, where potentially toxic concentration of nitrogen dioxide can accumulate.
Two relays with closing contact may be used for remote signalling or ventilation control. The default alarm set-points are typically at 3 ppm and at 6 ppm.
The instrument utilises novel fully calibrated and temperature compensated electrochemical gas sensor with excellent repeatability, stability and long lifetime.
Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.
Nitrogen Dioxide Detector
Calibration | Nitrogen Dioxide NO2 |
Sensing method | Long-life electrochemical sensor |
Sampling method | diffusion |
Detection range | Standard 0...20 ppm (100 ppm peak) NO2 |
High 0...200 ppm (1000 ppm peak) NO2 | |
Resolution | 0,02 / 0,1 ppm NO2 |
Accuracy | < 1 ppm NO2 |
Sensor lifetime | > 2 years |
Power supply | 11...30 VDC or 90...265 VAC |
Digital interface | RS485, Modbus RTU protocol |
Analog outputs | 2 × 4-20 mA / 0-10 V, user settable |
Output relays | 2 × SPST relays (closing contact), |
250 VAC / 30 VDC, 5 A max | |
Default alarm set-points | 3 ppm /6 ppm NO2 |
Enclosure | Light grey ABS plastic, wall mount, IP65 |
Dimensions | H85 × W82 × D55 mm |
Operating conditions | -20...+50 °C, 15...90 %RH |