Carbon monoxide detector
Carbon Monoxide detector E2608-CO is a member of new PluraSens® family of multifunctional measurement instruments.
Applications include underground parkings, boiler houses, kitchens, and other confined spaces, where potentially toxic concentration of carbon monoxide can accumulate.
Two relays with closing contact may be used for remote signalling or ventilation control. The default alarm set-points are typically at 25 ppm and at 35 ppm.
The instrument utilises novel fully calibrated and temperature compensated electrochemical gas sensor with excellent repeatability, stability and long lifetime.
Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.
Carbon monoxide detector
Calibration | Carbon Monoxide CO |
Sensing method | Long-life electrochemical cell |
Sampling method | Diffusion |
Detection range | 0...1000 ppm CO |
Resolution | 1 ppm CO |
Accuracy | ± 5 ppm CO |
Sensor lifetime | > 7 years |
Power supply | 11...30 VDC or 90...265 VAC |
Digital interface | RS485, Modbus RTU protocol |
Analog outputs | 2 × 4-20 mA / 0-10 V, user settable |
Output relays | 2 × SPST relays (closing contact), |
250 VAC / 30 VDC, 5 A max | |
Default alarm set-points | 25 ppm / 35 ppm CO |
Enclosure | Light grey ABS plastic, wall mount, IP65 |
Dimensions | H85 × W82 × D55 mm |
Operating conditions | -40...+85 °C, 0...100 %RH |